Message
×
loading..
JH6000HQ-D4 series  SF6 mixed gas comprehensive detector
  • JH6000HQ-D4 series  SF6 mixed gas comprehensive detector

JH6000HQ-D4 series SF6 mixed gas comprehensive detector

 ?
recommendation index:
Detection function, high accuracy, good stability
Portable design, fast testing, low air consumption, environmentally friendly
Automatic flow control, efficient and accurate, effectively reducing sample gas emissions
Users can use standard gas to self-calibrate the instrument
  • Detect the main decomposition products of insulation material cracking inside SF6 mixed gas electrical equipment: SO2 ,SOF2 , H2 S,CO,NO, N2 O,NF3 ,HF and other contents

  • Detect SF6 purity, SF6/N2 or SF6/CF4 mixing ratio, gas humidity in SF6 electrical equipment

  • JH6000HQ-D4 series SF6 mixed gas comprehensive detector, including JH6000HQ1-D4 (SF6/N2), JH6000HQ2-D4 (SF6/CF4) and JH6000HQ3-D4 (SF6/N2, SF6/CF4) and other models

  • NO, N2O, NF3 are optional

name

component

parameter

Model

JH6000HQ1-D4

JH6000HQ2-D4

JH6000HQ3-D4

minimum detectable quantity

SO2+SOF2、H2S、HF

≤0.1μL/L

CO、NO、N2O、NF3

≤0.5μL/L

SF6

≤0.01%

N2

≤0.01%

\

≤0.01%

CF4

\

≤0.01%

≤0.01%

O2

≤0.001%

dew point

≤0.1℃

precision

SO2+SOF2、H2S、HF

measurement value ≤ 10 μL/L, error≤±0.5 μL/L

measured value > 10 μL/L, error±5%.

CO、NO、N2O、NF3

measurement value≤ 50 μL/L, error≤±2.0 μL/L

measurement value > 50 μL/L, error≤±4%

SF6

Pure gas ≤ ± 0.1% (W/W)

Air mix ≤ ± 0.5%

N2

≤±0.5%

\

≤±0.5%

CF4

\

≤±0.5%

≤±0.5%

O2

≤±0.05%

Dew point: resistance/mirror

≤±1℃/0.3℃

repeatability

SO2+SOF2H2S、HF

measured value ≤ 10 μL/L, ≤ 0.2 μL/L

10μL/L~100μL/L:2%.

CO、NO、N2O、NF3

measured value  ≤ 50 μL/L, ≤ 1.5 μL/L

detection value 50 μL/L ~1000 μL/L: ≤ 3%

SF6

pure gas

≤0.05%(W/W,RSD)

air mix

≤1.0%(RSD)

O2

≤1.0%(RSD)

N2

≤1.0%(RSD)

\

≤1.0%(RSD)

CF4

\

≤1.0%(RSD)

≤1.0%(RSD)

dew point

1%

range

SO2+SOF2

0~100μL/L,0~2000μL/L

H2S

0~100μL/L

HF

0~20μL/L

CO、NO、N2O、NF3

0~1000μL/L

SF6

0~100%

N2

0~100%

\

0~100%

CF4

\

0~80%

0~80%

O2

0~1%

dew point

-80 ℃~ + 20 ℃ (resistance and capacitance)/-60 ℃~ + 20 ℃ (mirror)

gas flow rate

Decomposition, mixing ratio

200±5%mL/Min  

moisture

500±10%mL/Min   


Related recommendations

JHRXLK-300 SF6 Infrared Gas Leak Detection Temperature Imager

Both gas imaging leak detection and infrared temperature measurement

JHRX series, infrared thermal imaging cameras

Expert-level native analysis capabilities assist in diagnosing equipment status

JHSP-30 SF6 Portable Helium Ion Detector

Highly integrated all-in-one design

JHZW-100, UV Imager

All-day blind ultraviolet imaging technology

Add wechat

Scan and add customer service wechat

九九99久久精品国产,久久精品免费精品视频碰碰,免费精品国产自产拍在线观看,精品一区二区三区在线视频观看
久久99精品麻豆国产 | 亚洲国产一区二区三区在线 | 一本色道久久88综合亚洲精品 | 日本乱码视频免费播放性爱 | 亚洲欧洲美婷婷久久 | 思思久久99热这里精品66 |